CABLE DATA FORM - CABLE PROPERTIES

Name                  Name of the cable type. The name is limited to 40 characters. This name must be unique.

Outside radius    The cable’s overall radius.

Permeability       The relative permeability of the conductor and sheath is equal to 1.0 because they are typically made of non-magnetic metal such as cooper or aluminum. Refer to APPENDIX B:  CABLE DATA for more information on permeability. If cable does not have one or more component such as armor, serving or oversheath, leave the corresponding permeability field blank.

Inner and outer radii        Enter zero for the inner radius if the conductor is solid. If cable does not have armor, leave armor radius fields blank.

Resistivity          The unit of resistivity is microOhm-centimeters for both English and metric libraries.  Refer to APPENDIX B:  CABLE DATA for more information on resistivity. If cable does not have armor, leave armor resistivity field blank.

Semiconductor layer        Enter thickness of the semiconductor layer. Enter zero if cable does not have these layers.

Center distance  Distance between centers of the 3-core cable and phase conductor

Theta                  The center of the 3-core cable is the pole of the polar coordinates.  Theta is the angle in degree.
theta

Note: Modifying the cable properties will affect line constants results of all lines in the database that utilize that cable type.