A: OneLiner V15.10 release introduced critical updates to the network iterative solution engine to resolve calculation flaws identified in previous versions. These improvements target the accuracy of fault simulation in networks containing specific nonlinear elements under defined conditions.
Impacted Networks
Users are advised to scrutinize fault simulation results for networks exhibiting the following configurations:
•CIR models configured with negative-sequence current outputs for unbalanced faults that reach the device's current limits.
•CIRs and/or Type-3 wind plant models located in electrical proximity to lines equipped with MOV-protected series capacitors, where the fault current exceeds the MOV protection threshold
•CIRs and/or Type-3 wind plant models located in electrical proximity to generators with current limits, where the generator output to faults reaches the limit.
Legacy Logic and Backward Compatibility
To maintain consistency with historical data, OneLiner V15.10 handles legacy files as follows:
•Automatic Detection: When opening network files with CIR models saved in earlier versions, the program defaults to the original solution logic.
•Result Consistency: This ensures that legacy simulations produce results identical to those from previous software versions.
•Manual Override: To apply the V15.10 logic improvements and bug fixes to these legacy files, users must manually select either Default or Custom convergence criteria in the Fault | Option dialog box.
Recommendations
1. Software Update: Upgrade to the latest build of OneLiner V15.10, which includes improved iterative solution logic.
2. Parameter Configuration: Review and update the customized fault simulation settings in existing network files to enable the improved simulation engine, by manually selecting either Default or Custom convergence criteria in the Faults | Options dialog box.
3. Study Result Audit: Reevaluate previous studies involving the aforementioned nonlinear elements to assess the impact of potential calculation errors.