9.11  CONVERTER-INTERFACED RESOURCE DATA

This section contains parameters of converter-interfaced resource. The first line in the section must say:  [CONVERTER-INTERFACED RESOURCE DATA].  This is followed by the data described below.  A blank line ends the section.  The terms “voltage” and “current” below refer to positive-sequence voltage and current unless specified otherwise.

1.  Bus Name: Name of the bus to which the current source is attached, in quotation marks.  

2.  Base kV: Nominal kV of the current-source bus.

3.  In-Service Flag: 1 if the current source is in service; 0 if it is not.  The default value is 1.

4.  Number of units: Number of type-4 wind generators or solar inverter units in this plant.

5.  Unit MVA Rating

6.  Unit rated MW.

7.  Unit MW generation.

8.  Reserved field: Enter a constant 0..

9.  Maximum current output when voltage is higher than the threshold as a multiple of the full load current

10.     Maximum current output transition voltage threshold

11.     Maximum current output when voltage is lower than the threshold as a multiple of the full load current

12.     Low voltage generator shutdown threshold in per-unit

13.     High voltage generator shutdown threshold in per-unit

14.     Reserved field: Enter a constant 0

15.     Slope of the positive-sequence reactive injection characteristics

16.     Slope of the negative-sequence reactive injection characteristics

17.     Reserved field: Enter a constant 0

18.     In-service Date: Set to 0 if not available. Otherwise enter an unsigned 32-bit integer that store the year/month/date information given by the CTime object in Microsoft Foundation Class.

19.     Out-of-Service Date: Set to 0 if not available. Otherwise enter an unsigned 32-bit integer that store the year/month/date information given by the CTime object in Microsoft Foundation Class.

20.     Reserved field: Enter a constant 0

21.     Reserved field: Enter a constant 0

22.     Reserved field: Enter a constant 0

23.     Reserved field: Enter a constant 0

24.     Memo and Unit sets aggregation info: Comments with a maximum of 512 characters, and the unit sets aggregation info separated by the pre-defined header text of ‘***Aggregation Info***’ (no quotes). Any alpha-numeric characters can be used, except the following characters must be included in escaped form of: \q for the string delimiter (single or double quotation mark); \n for new line. Data for each unit set is entered on a single row and consists of four space delimited fields: ID, Name, MVA and Memo. The MVA must be zero or positive number. The other aggregation info fields are alpha numeric and must be enclosed in quotation marks in escaped form. The entire field is enclosed in quotation marks (see example below).

25.     Tags: Tag string with a maximum of 512 characters.  Tags in string are separated by semicolon. Any alpha-numeric characters can be used, except for the string delimiter (single or double quotation mark).  The tag string is enclosed in quotation marks.

26.     UDF: User-defined data fields. Enter the list of user defined field values as a tab delimited text string enclosed in single quotes.

An example voltage controlled current source data section is shown below.

 [1LPF CONVERTER-INTERFACED RESOURCE DATA]

'TENNESSEE' 132 = 1 2 13.5 1.8 0 1.1 0.5 1.1 /

0 1.2 0.1 2 0 0 0 0 0 0 0 0 /

'This site has some units yet to be built ***Aggregation Info***\n\qUnit 1\q \qUnit name 1 long\q 13 \qMemo of unit i\q\n\qUnit 2\q \qUnit name 2 long\q 15 \qMemo of unit 2\q\n\n' /' /

 '' ''